Earth leakage explained

Earth leakage explained

What is earth leakage? Earth leakage can be divided into two categories.

What Is Earth Leakage?

The first is unintentional earth leakage, which results from faulty equipment or insulation. The second is intentional earth leakage, which occurs as consequence of equipment design. Whatever the source of earth leakage, it must be prevented from causing electric shocks, either by making provision for automatic disconnection of the supply ADSor by using isolated power systems IPSs that incorporate insulation monitoring devices IMDs.

The first method is the most common and is usually based on RCDs residual current devices or RCBOs residual current circuit breakers with overcurrent protection. RCDs and RCBOs monitor the current flowing in the line conductor s and comparing this with the return current in the neutral conductor. The best way to tackle this sort of problem is to measure the earth leakage current, which is most easily done with an earth leakage clamp meter.

This is clamped round the line and neutral conductors only NOT the protective conductor and will measure the difference between the line and neutral currents, which is the earth leakage current see image at top of page.

This test can be performed at various places in an electrical installation: at the incoming cables, at each outgoing circuit from a distribution board, at midpoints on a radial circuit where live and neutral conductors are accessible, and at connected equipment. The procedure for deciding which circuit is causing nuisance tripping in a domestic or small commercial installation is to turn off all the MCBs in the consumer unit, and position the earth leakage clamp around the mains incoming cables.

Turn on each circuit in turn until a circuit is found that causes the measured earth leakage current to increase significantly. This is likely to be the problematic circuit. The next step is to decide whether the leakage is intentional or unintentional. To check this, perform an RCD ramp test. Hopefully, this article has shed a little light on earth leakage and helped contractors to ensure installations are safe, and to tackle nuisance tripping which, as the name suggests, can be really annoying!

This article aims to provide guidance on the safe and accurate use of electrical testing equipment. This guide considers the measurement and calculation of the prospective short-circuit current and prospective earth fault current at the origin and at other relevant points in the installation.

Also on start up, some equipment generates a surge, which can trip the earth leakage protection. This can be achieved by manual switching, or by installing delay relays for automatic staged start up. Alternatively as mentioned in the article,if possible you could split the load over a number of circuits, so the Earth leakage is shared over a number of Earth leakage devices. I come across this sort of problem quite often.

When they are isolated the problem disappears. Also pat testing does reveal large amounts of leakage current. So I tell customers either invest in new appliances or I can run a separate circuit without the RCD protection. Most of the time customers opt for new appliances. I got to get me a leakage clamp meter soon. Anyways very helpful advice guys. Cheers for that!. I belive the regs now states that every domestic circuit has to be rcd protected regardless of how the cabling is installed.

I would certainly recommend to anyone to invest in a earth leakage clamp meter as they are such a useful tool in a world full of rcds and lots of appliances.

I have installed a 10 way contactom with rcbo's. The device is considered to be [faulty] if it operates below 15mA or only exceeding 30mA. Che Kuan Yau Singapore. Just out of curiosity I isolated a distribution board and measured earth leakage by clamping the line and neutral conductors.

I measured 70mA.There is a new 18 th Edition regulation identifying the requirement for you to measure Earth Leakage, as stated in BS Reg In a nutshell, each electrician must check that each install completed does not have excessive leakage to earth on each of the RCDs or RCBOs.

The Di-LOG DL Earth Leakage Clamp is a low-cost solution that works on differential leakage measurement, which involves simultaneously clamping around the live and neutral conductors together. Where possible, you will need to have the day-to-day electrical appliances in operation to accurately determine potential issues. You then repeat for each RCD. Intentional Earth Leakage tends to be found in electrical appliances in the form of a functioning earth, where a small amount of earth leakage is required for the appliance to function.

Unintentional Earth Leakage tends to occur in poor installations where there could be a breakdown in the conductor insulation or moisture ingress, amongst many other causes. Switching each individual circuit off, one-by-one, is a good area to start. Here you can easily identify which circuit you may need to investigate further.

Di-LOG has created a dedicated web page for readers of this article, containing all of the details you need to know about the DL Earth Leakage Clamp, including special offers and technical specs.

SPD technology: where should it be used? ECA 2 April, Commerical surge protection: what to consider? Hager 20 March, Di-LOG 13 March, Ensuring installations are fully compliant Marshall-Tufflex 5 March, HellermannTyton launches new Metal Fixings range 20 January, Safety first with 18th Edition changes 13 December, All Rights reserved.The discussed Earth leakage circuit breaker diagrams will monitor the leakage current level of the earthing line of your house electrical sockets and will trip the appliances as soon a fault is detected.

Here we will learn 2 designs, first using transistors only and the second using IC LM If anything goes wrong with them it will instantly switch off the mains and stop any further associated loss. A simple ELCB circuit is discussed here. A simple circuit of an Earth leakage circuit breaker also called ground fault circuit interrupter is discussed in this article. The circuit will immediately switch off the mains on detecting a missing earth connection or a current leakage through the appliance body.

A leaking current through earth terminal is probably more dangerous than a short circuit in a domestic wiring. But earth current leakages may remain hidden for years, eating up your precious electricity and also weakening or deteriorating the wiring conditions and also the appliances. Moreover if the earth connection is not properly grounded due to improper conduction or breakage, the leakage may turn into a lethal shock over the body of the appliance. Commercially available earth leakage circuit breaker units are very costly and bulky, involving complicated installation procedure.

I have designed a simple circuit which is low in cost and yet handles the situation handsomely. The device will detect any current exceeding above 5mA through the earth passage and switch off the mains. The connected appliance will then need a diagnose or a total elimination. A leaking appliance not only wastes your electricity but also can be dangerous fatally.

earth leakage explained

The proposed ground fault circuit interrupter or ELCB utilizes a simple principle of detecting the AC signal rather the applied or the leaking voltage. Here, the leaking AC may be too small to be detected as a potential difference using simple voltage detection configuration, therefore the leakage is effectively sensed as a frequency, using a simple audio amplifier stage.

As shown in the diagram, a simple bootstrapped amplifier network forms the main sensing stage of the unit. Transistors T1 and T2 along with the associated passive components are wired up into a small two stage amplifier. The introduction of R3 becomes very crucial as it provides a positive feed back to the input making the circuit more stable and respond to minutest input signals.

The inductor L1 basically has two windings, the primary which is connected to the earth point of the socket has less number of turns, the secondary winding has six times more number of turns and is integrated to the input of the circuit via C1.

The role of L1 is to amplify any AC induced into its primary winding which can only happen in case of a leakage through the body of an appliance connected to the socket.

The above amplified leakage voltage is further amplified to a level enough to activate RL1, instantly disabling the input to the appliance and indicating the earth leakage fault. Capacitor C5 along with D3 and C4 forms a standard transformerless power supply to power the circuit.

D3 performs a dual function of rectification and surge suppression. Interestingly the main earth connection itself becomes the negative of the circuit instead of the neutral line. Also since RL2 is directly connected to the supply across the positive of the circuit and the earthing, simply means that if the earthing becomes weak or disconnected, the relay will deactivate, cutting off the AC mains to the appliance, so it effectively indicates the health of the earthing and safeguards the house from faulty or missing earth connections.

Now using 32 SWG copper wire, wind turns over the primary winding, as before tie the ends to the other side of the bobbin by soldering. Insert and fix the coil within the E-cores.

Secure it tightly using PVC tape. Normally electromechanical concepts are employed for making these devices, however here we will see how an ELCB can be made by using ordinary electronic components; we will also see why an electronic counterpart is more efficient than the commercial electromechanical units. There are three versions through an electronic ELCB can be made, the first uses a relay for the switching actions, the second idea incorporate a Triac and the third concept employs a SSR or a solid state relay for the required implementations.

For all the above concepts, the triggering feature remains the same, through an input inductor stage. Looking at the figure we can see that the entire circuit is concentrated around a single Opamp from the IC The opamp is configured as a high gain inverting amplifier.

The opamp is configured as a high gain AC amplifier and its sensitivity can be adjusted by varying the value of R2, increasing its value increase the sensitivity of the circuit. Any minute AC signal that may be present at the inverting input 2 of the IC is picked via the coupling capacitor C1 and instantly amplified by the IC. A small inductor transformer is wired across the above input of the IC. The primary of the inductor is connected to the wire which finally terminates to the earthing terminal or the pin of the various 3-pin sockets in the premise.

In case of a leakage, the leaking current passes through the primary winding of the inductor and gets stepped up at the secondary winding.An Earth-leakage circuit breaker ELCB is a safety device used in electrical installations with high Earth impedance to prevent shock. It detects small stray voltages on the metal enclosures of electrical equipment, and interrupts the circuit if a dangerous voltage is detected. The main purpose of Earth leakage protectors is to prevent injury to humans and animals due to electric shock.

This is a category of devices, which are used to protect instruments, circuits and operators, while Earth leakage. Voltage sensing ELCBs were first introduced about sixty years ago. Current sensing ELCBs were first introduced about forty years ago. But the use of a common name for two different devices gave rise to considerable confusion in the electrical industry. If the wrong type was used on an installation, the level of protection given could be substantially less than that intended, in particular the voltage operated type can only protect against faults or shocks to metalwork connected to the circuit ground, connected to the VOELCB, it cannot detect current leaving a live wire and running to ground by another path, such as via a person standing on the earth.

Residual current refers to any residue when comparing current in the outbound and return currents in the circuit. In a single phase circuit this is simply the live or phase current minus the neutral current. In a 3 phase circuit all current carrying conductors must be sensed.

An ELCB is a specialised type of latching relay that has a building's incoming mains power connected through its switching contacts so that the ELCB disconnects the power when earth leakage is detected. The ELCB detects fault currents from live to the Earth ground wire within the installation it protects. If sufficient voltage appears across the ELCB's sense coil, it will switch off the powerand remain off until manually reset.

Voltage ELCBs have been in widespread use since then, and many are still in operation but are no longer installed in new construction. A voltage-operated ELCB detects a rise in potential between the protected interconnected metalwork equipment frames, conduits, enclosures and a distant isolated Earth reference electrode.

They operate at a detected potential of around 50 volts to open a main breaker and isolate the supply from the protected premises. A voltage-operated ELCB has a second terminal for connecting to the remote reference Earth connection. One terminal goes to the installation Earth CPC circuit protective conductor, aka Earth wireand the other to the Earth rod or sometimes other type of Earth connection.

earth leakage explained

Compared with a current-sensing system, voltage sensing systems have several disadvantages which include:. An RCCB typically consists of a current transformer, which has multiple primary windings and one secondary winding. Neutral and line or lines in multiple phase systems wires act as the primary windings. A wire wound coil is the secondary winding. The current through the secondary winding is zero at the balanced condition.Sunpower Electronics has over 25 years of trading experience with power supplies, designing products for manufacturing to provide effective, powerful and long-lasting solutions for our clients.

Should you be unsure and need support choosing the correct power supply for your project then get in touch today. We offer many services including bespoke power supplies designed specifically for your manufacturing projects needs, alternatively you can browse our current product ranges.

Leakage current is the current that flows from either AC or DC circuit in equipment to the chassis, or to the ground, and can be either from the input or the output.

If the equipment is not properly grounded, the current flow through other paths such as the human body. This may also happen if the ground is inefficient or is interrupted intentionally or unintentionally.

The leakage current in equipment flows when an unintentional electrical connection occurs between the ground and an energized part or conductor. The ground may be the reference point of zero voltage or the earth ground. Ideally, the current leaking from the power supply unit should flow through the ground connection and into the installations earth ground. Leakage current in laptops or devices using two pin plugs is mostly through the signal cables connected to other grounded or ungrounded equipment such as printers.

The other equipment provides a path to the ground if it is properly grounded or may give an electric shock to anybody touching the exposed metal parts if not properly earthed. The leakage in devices is largely due to the imperfections in the insulators or materials that make the component such as the semiconductors and capacitors. These results into small current leaking or flowing through the through the dielectric, in the case of a capacitor.

Leakage current in power supplies may occur due to the EMC filters, which utilizes Y capacitors between the live and neutral conductors. This causes some leakage current to flow from the neutral or the live conductor to the power supply casing which is normally connected to the earth ground.

Most power supply manufacturers specify this current which should always be lower than 3. This ensures that the current is very low and cannot harm the person who touches or comes into contact with the power supply case. A power supply with a good earth ground reduces the leakage current significantly by providing a low resistance path to the ground. The filter manufacturers usually specify the maximum leakage current that the filter will leak, but these are only theoretical values and the actual values may deviate from these especially if parameters such as voltage or frequency change.

To get an accurate value of the leakage current, it is advisable to measure the current that flows to the ground when the filter is in operation. There are standards that specify maximum leakage currents that are safe for humans under different conditions.

These vary with the application and type of possible contact as well as the type of ground connection. Designers are supposed to ensure that the leakage current does not harm the users who touch the enclosure of a power supply or the powered equipment. All applications have their upper limit on the current that should flow. Medical equipment and other sensitive equipment are required to have very low currents due to the nature of their applications and the impact they can have.

The standards are more stringent in medical applications since the weak patients are more vulnerable to electric shocks which can be fatal. The permissible leakage current under normal conditions is 0. The leakage current is very dangerous if it exceeds the permissible safe limit. It is even worse in medical applications due to both the risk it poses to both patients and caregivers. Only a small current needs to flow through the human body to cause harm and can be fatal for patients whose immune systems are already weak.

View our Medical Grade Power Supplies here. Must have a protection against the electric shock by means of basic insulation in combination with a protective earth ground connected to the equipment case. These equipment do not have a protective earth ground.The domestic mains supply is one of three phases generated at the power station. The generator windings are arranged in what is called a "star" configuration.

Earth leakage circuit breaker

This means that one end of each phase winding is connected together. This common connection is connected to Earth. So, instead of having six wires from the generator two for each phase winding there are four. The common connection, called neutral, and the other three wires, one for each phase. Usually identified as red, yellow and blue. A domestic mains supply will have two wires coming in from the generating station or from a switch-yard or sub-station or whatever else it might be calledone wire from a phase and one wire from the neutral.

The phase is often called the line, "live" or "hot". Although a connection to Earth is made at the consumer's premises, it is not necessary for any appliance to function. It will be ignored for the moment.

In normal operation, current from the generator passes through whatever load is switched on and back to the generator. Normal operation is illustrated in these two pictures. If, because of a fault, the mains supply gets connected to a conducting part of the load, the metal body of a washing machine for example, the appliance becomes "live".

In other words there will be a voltage difference the mains voltage between the appliance and Earth. Anyone touching the appliance and standing anywhere, or on anything, with a conductive or partially conductive path to Earth will be subject to an electric shock.

The next two pictures illustrate this. To minimise the risk from such faults any exposed conductive parts of an appliance are connected to Earth via a third pin on the appliance's plug. Under a fault condition there can then be no voltage between the appliance's exposed conductive parts and Earth. The fault, however, still exists. Extra protection is afforded by including in the supply a device which is known by several names.

Those I know about are:. It shouldn't be necessary, but experience has taught me to err on the side of prudence so I shall explain what a "miniature circuit breaker" is.

A miniature circuit breaker, or indeed any other 'ordinary' circuit breaker, miniature or not, is simply an electro-mechanical replacement for a fuse.

Effectively a re-settable fuse. I have come across people, people who should have known better, who thought that they gave protection against earth leakage faults. They don't. A GFI, or whatever other fancy name you know it by, is a differential current detector.

It detects any difference between two currents. The current in the supply line, the "hot" lead, and the current in the neutral lead. If a difference of greater than its design figure is detected it then behaves as a circuit breaker and switches off the supply. The next two pictures hopefully make this clearer.Register now or log in to join your professional community.

Earth leakage is concerned with the insulation of the cable. More bad insulationmore leakage current measured in mA. The ground fault is the current which can flow due to Short circuit of conductor to Ground, or it could be a current measured by a ground CT connected at individual phases or all three phases can pass through the Ground CT.

In case of earth leakage, a live phase may have come in contact with the device that contains it but which itself is not in contact with the ground, resulting in no fault current just yet.

But it begins to flow the moment any person touches it, leading to what we call electrocution. Earth leakage is a current that flows through depreciated conductor insulation like if already old cable and then the insulation will slowly conduct flow of current to grounded parts of electrical equipment because the resistance of the insulation was lowered.

Meanwhile ground fault is when current carrying conductor directly touches any grounded part of the electrical equipment and activating ground fault protection devices. Ground fault is a fault when phase touches ground or any conductive material which is directly connected to earth, it is called ground fault.

Products By Bayt. Use Our Mobile App. Get Fresh Updates On your job applications, and stay connected. Download Now. Start networking and exchanging professional insights Register now or log in to join your professional community.

Follow What is the difference between earth leakage and ground fault? Engineering Electrical Engineering. Upvote 1 Views Followers 8. Write an Answer Register now or log in to answer. Upvote 2 Downvote 0 Reply 0.

Upvote 1 Downvote 0 Reply 1. Answer added by ahmed ali faris, electromechanical mangerI Engineering Co. Upvote 1 Downvote 0 Reply 0. Answer added by gaber oraby, Maintenance Electrical EngineerEl-mustathmir food industry 4 years ago.

earth leakage explained

Upvote 0 Downvote 0 Reply 0. See More Answers.